Table 2
(print from .pdf)
Effective September 17, 2009
Updates All Previous Table
Single Phase, Single Position
UNDERGROUND ENTRANCE
200, 400 or 600 Amp, 120/240 or 208/120 Volt
4 or 5 Terminal
200 or 400 Amp, 240/480 or 480/277 Volt
5 Terminal
|
MFG. & CATALOG # |
5TH TERMINAL ACCESSORY IF REQUIRED |
SERVICE AMPS |
DIMENSIONS (INCHES) |
TERMINAL SIZE (AWG OR KCMIL) |
BYPASS TYPE |
|
|
SEE NOTE #2 |
|
|
MIN. |
MAX |
|
|
CUTLER HAMMER |
|
1004884A-CH |
ARP00035CHJ |
200 |
13x13x5 |
8 |
350 |
Horn |
|
1004984A-CH |
ARP00326CH |
400 (Cl 320) |
36 x15x6 |
See Note #9 |
Lever |
|
DURHAM (See Note #8) |
|
1004884A |
ARP00035 |
200 |
13x13x5 |
8 |
350 |
Horn |
|
1004984A |
ARP00326 |
400 (Cl 320) |
36 x15x6 |
See Note #9 |
Lever |
|
LANDIS & GYR (See Notes #7 & #8 ) |
|
UAS817-PPGP |
659-0121 |
200 |
14x13x5 |
6 |
350 |
Horn |
|
HUAS817-PPGP |
659-0121 |
200 |
14x13x5 |
6 |
350 |
Horn |
|
UAS877-PPGP |
659-0121 |
200 |
14x13x5 |
6 |
350 |
Horn |
|
HUAS877-PPGP |
659-0121 |
200 |
14x13x5 |
6 |
350 |
Horn |
| 1004984A |
----------- |
400 (Cl 320) |
28 x15x6 |
|
Lever |
|
44704-82 |
----------- |
400 (Cl 320) |
34x20x6 |
See Note #9 |
Lever |
| 44704-82PP |
----------- |
400 (Cl 320) |
34x20x6 |
|
Lever |
| 9810-9802 |
----------- |
600 (Cl 480) |
|
|
Bolt-In |
|
MIDWEST |
| 1004884A-MEP |
ARP00035MEP |
200 |
13x13x5 |
8 |
350 |
Horn |
| 1004984A-MEP |
ARP00326MEP |
400 (Cl 320) |
36 x15x6 |
|
Lever |
|
MILBANK |
|
U1980-0-KK-BL |
5T8K2 |
200 |
15 x 13x4 |
2 |
350 |
Horn |
|
U4413-0-KK |
5T8K2 |
200 |
15 x13x4 |
2 |
350 |
Horn |
|
U3939 |
----------- |
400 (Cl 320) |
30x15 x5 |
See Note #9 |
Lever |
|
U3126-0-KK-BLG |
5T8K2 |
200 |
15 x 13 x 4 |
2 |
350 |
Horn |
|
MURRAY |
|
RL199A |
RX112FJ |
200 |
14x13x5 |
6 |
350 |
Horn |
|
RL199CJ |
RX112FJ |
200 |
14x13x5 |
6 |
350 |
Horn |
|
SIEMENS |
|
SUAS817-PPGP |
659-0121 |
200 |
14x13x5 |
6 |
350 |
Horn |
|
SUAS877-PPGP |
659-0121 |
200 |
14x13x5 |
6 |
350 |
Horn |
|
S44704-82 |
----------- |
400 (Cl 320) |
34x20x6 |
See Note #9 |
Lever |
|
S44704-82PP |
----------- |
400 (Cl 320) |
34x20x6 |
See Note #9 |
Lever |
|
SQUARE D |
|
1004884A-SQD |
ARP00035SQD |
200 |
13x13x5 |
8 |
350 |
Horn |
|
1004984A-SQD |
ARP00326SQD |
400 (Cl 320) |
36 x15x6 |
See Note #9 |
Lever |
MOST RECENT CHANGES
|
DATE |
MFG. |
CATALOG # |
STATUS |
REASON |
|
09/2009 |
Landis & Gry |
9810-9802 |
Approved |
New Equipment |
NOTES:
|
1. |
All meter bases listed in this table are "ringless" style. Horn bypasses are required in all ringless bases. Class 320 bases must contain a lever bypass rated 100% continuous duty. |
|
2. |
Meter bases used for 208/120 volt, 3 wire services must have a 5th terminal installed in the 9 o'clock position. The catalog number for the 5th terminal is listed in the "5th Terminal Accessory" column in the table and must be specified when purchasing the meter base. |
|
3. |
The manufacturer's catalog number must be stamped on the outside of the meter base so that it will be visible after the base is installed. The number must not be stamped on the cover. |
|
4. |
When aluminum conductors are used, the electrical contractor must apply the corrosion inhibiting compound recommended by and in the manner prescribed by the cable manufacturer. |
|
5. |
The line (utility) terminals in all UG bases must be offset to the left or right of the socket to accommodate the installation of underground service wires. |
|
6. |
Conduit Requirements: |
|
|
200 Amp Service The conduit KO directly under the line (utility) terminals must accept a 3 inch conduit. |
|
|
400 Amp (Cl 320) Service The conduit KO directly under the line (utility) terminals must accept a 4 inch conduit. The conduit KOs directly under the load terminals must accept two (2) 3 1/2 inch conduits. |
| |
600 Amp (Cl 480) Service The bottom of the base must contain a minimum of three (3) 4 inch conduit KOs. The left side and center KOs are for PPL use only. |
|
7. |
Prefix "H" on Landis & Gyr (L&G) bases indicates bases that are sold through national retailers. |
|
8. |
L&G Underground Base #UAS817-PPG and HUAS817-PPGP has line terminals mounted on right side of base. Durham UG Base #1004884 is available with line terminals mounted on right or left side of base (specify when ordering). All other bases have line terminals mounted on left side of base. |
|
9. |
Class 320 Meter Bases:
- All 320 amp meter bases contain stud terminals.
- Only UL approved lay-in or box style connectors suitable for use with copper or aluminum conductors can be installed for wire termination on the studs.
- Compression connectors are not permitted.
|
CLASS 320 METER BASE
CONNECTOR REQUIREMENTS
|
|
Line Side Terminals |
Line Side Neutral Terminals |
Load Side Terminals |
|
WIRE RANGE |
Single Only #350 - 750 Kcmil |
#4/0 Awg - 500 Kcmil
|
Single--Up to 600 Kcmil Double--Up to 350 Kcmil |
APPROVED CONNECTORS FOR
CLASS 320 METER BASES
|
MFG. |
LINE SIDE TERMINALS & WIRE RANGE |
LINE SIDE NEUTRAL TERMINALS & WIRE RANGE |
LOAD SIDE TERMINALS |
|
CUTLER HAMMER |
ARP00129CH |
# 4 - 600 Kcmil |
ARP00129CH |
# 4 - 600 Kcmil |
Single - ARP00129CH Double - ARP00427CH |
| DURHAM |
ARP00129 |
# 4 - 600 Kcmil |
ARP00129 |
# 4 - 600 Kcmil |
Single - ARP00129 Double - ARP00427 |
|
LANDIS & GYR / SIEMENS |
56476 |
# 3/0-800 Kcmil |
60162 |
# 4/0-600 Kcmil |
Single - 60162 Double - 56732 |
| MIDWEST |
ARP00129MEP |
# 4 - 600 Kcmil |
ARP00129MEP |
# 4 - 600 Kcmil |
Single - ARP00129MEP Double - ARP00427MEP |
|
MILBANK |
*K3863 or K1540 |
350-800 Kcmil # 2-600 Kcmil |
K1540 |
# 2-600 Kcmil |
Single - K1540 Double - K1350 |
| SQUARE D |
ARP00129SQD |
# 4 - 600 Kcmil |
ARP00129SQD |
# 4 - 600 Kcmil |
Single - ARP00129SQD Double - ARP00427SQD |
10. Class 480 Meter Bases:
- All 480 amp meter bases contain stud terminals.
- Only L&G anti-rotational, box-style connectors can be installed for wire termination on the studs.
- Compression connectors are not permitted.
- Single or double port terminals are permitted on the line side studs.
- Single, double or triple port terminals are permitted on the load side studs.
- The left and center bottom knockouts in the base are for PPL use only.
- The connector stud on the left side of the ground bus is for PPL use only.
APPROVED CONNECTORS FOR
CLASS 480 METER BASES
|
|
|
LINE SIDE NEUTRAL TERMINALS |
|
|
LANDIS & GYR |
|
2-H56476 (3/0 - 800 Kcmil) |
|
2-H56476 (3/0 - 800 Kcmil) 1-H60162 (neutral) (# 4 - 600 Kcmil) |
|
|
|
2-H56732-M (#4 - 500 Kcmil) |
1-H56732-M (# 4 - 500 Kcmil) |
3-H56732-M (# 4 - 500 Kcmil) |
|
|
|
|
|
3-H68752-1 (# 6 - 250 Kcmil) |
11. All meter bases listed in this table are rated 600 volts AC unless otherwise noted.
* Connector size must be selected to accommodate PPL service lateral size.