Table 1

(print from .pdf)
 
Effective October 22, 2008
Updates All Previous Tables

SINGLE PHASE, SINGLE POSITION
OVERHEAD ENTRANCE
100, 200, 400 or 600 Amp 120/240 or 208/120 Volt
4 or 5 Terminal
200 or 400 Amp, 240/480 or 480/277 Volt
5 Terminal

MFG. & CATALOG #

5TH TERMINAL ACCESSORY IF REQUIRED

SERVICE AMPS

DIMENSIONS (INCHES)

TERMINAL SIZE (AWG OR KCMIL)

BYPASS TYPE

(See Note #2)

HxWxD

MIN.

MAX.

CUTLER HAMMER

1004162A-CH

ARP00035CHJ

100

10x8x3

8

2/0

Horn

1004161A-CH

ARP00035CHJ

200

14x8x4

8

250

Horn

1004159A-CH

ARP00035CHJ

200

15x11x4

8

350

Horn

1004984A-CH

ARP00326CH

400
(Cl 320)

36x15x6

See Note #6

Lever

DURHAM

1004162A

ARP00035

100

10x8x3

8

2/0

Horn

1004161A

ARP00035

200

14x8x4

8

250

Horn

1004159A

ARP00035

200

15x11x4

8

350

Horn

1004984A

ARP00326

400
(Cl 320)

36x15x6

See Note #6

Lever

LANDIS & GYR See Note #5

UAT111-OPGP

659-0121

100

11x8x3

6

2/0

Horn

HUAT111-OPGP

659-0121

100

11x8x3

6

2/0

Horn

UAT317-OPGP

659-0121

200

14x8x4

6

350

Horn

HUAT317-OPGP

659-0121

200

14x8x4

6

350

Horn

44704-82

--------

400
(Cl 320)

34x20x6

See Note #6

Lever

44704-82PP
--------
400
(Cl 320)
34x20x6
Lever

9810-9550
(300V AC)
See note #8

--------

600
(Cl 480)

36x17x6

See Note #7

Bolt-In

MIDWEST

1004162A-MEP
ARP00035
100
10x8x3
8
2/0
Horn
1004161A-MEP
ARP00035
200
14x8x4
8
250
Horn
1004159A-MEP
ARP00035
200
15x11x4
8
350
Horn
1004984A-MEP
ARP00326
400
(Cl 320)
36x15x6
Lever

MILBANK

U7487RL-KK-TG-BLG

5T8K

100

10x8x3

6

2/0

Horn

U7021RL-KK-TG-BLG

5T8K

200

15x8x4

6

250

Horn

MURRAY

RJ-193AXJ

RX112FJ

100

11 x8x3

6

2/0

Horn

RB-193CXJ

RX112FJ

200

14x8x4

6

350

Horn

SIEMENS

SUAT111-OPGP

659-0121

100

11x8x3

6

2/0

Horn

SUAT317-OPGP

659-0121

200

14x8x4

6

350

Horn

S44704-82

--------

400
(Cl 320)

34x20x6

See Note #6

Lever

S44704-82PP

--------

400
(Cl 320)

34x20x6

See Note #6

Lever

SQUARE D

1004162A-SQD

ARP00035SQD

100

10x8x3

8

2/0

Horn

1004161A-SQD

ARP00035SQD

200

14x8x4

8

250

Horn

1004159A-SQD

ARP00035SQD

200

15x11x4

8

350

Horn

1004984A-SQD

ARP00326SQD

400
(Cl 320)

36x15x6

See Note#6

 Lever

MOST RECENT CHANGES

DATE

MFG.

CATALOG #

STATUS

REASON

8/2008

Cutler Hammer

1004162A-CH

Approved

Updated Information

1004161A-CH
1004159A-CH
1004984A-CH
8/2008 Durham 1004162A Approved Updated Information
1004161A
1004159A
1004984A
8/2008 Midwest 1004162A-MEP Approved Updated Information
1004161A-MEP
1004159A-MEP
1004984A-MEP
10/2008 Midwest LRLPU412UALK Removed Obsolete
LQRLPU414BALK
8/2008 SquareD 1004162A-SQD Approved Updated Information
1004161A-SQD
1004159A-SQD
1004984A-SQD

 

NOTES:

 

1.

All meter bases listed in this table are "ringless" style. Horn bypasses are required in all ringless bases. Class 320 bases must contain a lever bypass rated 100% continuous duty.

2.

Meter bases used for 208/120 volt, 3 wire services must have a 5th terminal installed in the 9 o'clock position. The catalog number for the 5th terminal is listed in the "5th Terminal Accessory" column in the table and must be specified when purchasing the meter base.

3.

The manufacturer's catalog number must be stamped on the outside of the meter base so that it will be visible after the base is installed. The number must not be stamped on the cover.

4.

When aluminum conductors are used, the electrical contractor must apply the corrosion inhibiting compound recommended by and in the manner prescribed by the cable manufacturer.

5.

Prefix "H" on Landis & Gyr bases indicates bases that are sold through national retailers.

6.

320 Amp Meter Bases:

  • All 320 amp meter bases contain stud terminals.
  • Only UL approved lay-in or box style connectors suitable for use with copper or aluminum conductors can be installed for wire termination on the studs.
  • Compression connectors are not permitted.

320 AMP METER BASE
CONNECTOR REQUIREMENTS

Line Side
Terminals

Line Side
Neutral Terminals

Load Side
Terminals

WIRE
RANGE

Single Only
350 to 750 Kcmil

4/0 Awg to 500 Kcmil

Single--Up to 600 Kcmil
Double--Up to 350 Kcmil

APPROVED CONNECTORS FOR
320 AMP METER BASES

MFG.

LINE SIDE
TERMINALS

LINE SIDE
NEUTRAL TERMINALS

LOAD SIDE
TERMINALS

CUTLER HAMMER

ARP00129CH

ARP00129CH

Single - ARP00129CH
Double - ARP00427CH

DURHAM
ARP00129
ARP00129
Single - ARP00129
Double - ARP00427

LANDIS & GYR/SIEMENS

56476

60162

Single - 60162
Double - 56732

MIDWEST
ARP00129MEP
ARP00129MEP
Single - ARP00129MEP
Double - ARP00427MEP

MILBANK

K3863

K1540

Single - K1540
Double - K1350

SQUARE D
ARP00129SQD
ARP00129SQD
Single - ARP00129SQD
Double - ARP00427SQD

7. 480 Amp Meter Bases:

  • All 480 amp meter bases contain stud terminals.
  • Only L&G anti-rotational, box-style connectors can be installed for wire termination on the studs.
  • Compression connectors are not permitted.
  • Single or double port terminals are permitted on the line side studs.
  • Single, double or triple port terminals are permitted on the load side studs.
  • All overhead entrance bases have two (2) hub openings on top of the base.

APPROVED CONNECTORS FOR
480 AMP METER BASES

MFG.

LINE SIDE
TERMINALS

LINE SIDE
NEUTRAL TERMINALS

LOAD SIDE
TERMINALS

LANDIS & GYR

Single Port Kit

2-H56733
(3/0 - 800 Kcmil)

1-H56476
(3/0 - 800 Kcmil)

2-H56477
(3/0 - 800 Kcmil)
1-H60162 (neutral)
(#4 - 600 Kcmil)

Double Port Kit

2-H56427M
(#2 - 500 Kcmil)

1-H56732M
(#4 - 500 Kcmil)

2-H56425M
(#4 - 500 Kcmil)
1-H56732M (neutral)
(#4 - 500 Kcmil)

Triple Port Kit

Not Permitted

Not Permitted

2-H68752-1
(#6 - 250 Kcmil)
1-#H68752-1 (neutral)
(#6 - 250 Kcmil)

 8.  All meter bases listed in this table are rated 600 volts AC unless otherwise noted.