TABLE 11

(print from .pdf)

Effective April 15, 2008
Updates All Previous Tables

 

SINGLE PHASE, SINGLE POSITION
METER SOCKET/LOAD CENTER
OVERHEAD & UNDERGROUND ENTRANCE
120/240 or 208/120 Volt
100, 200 or 320 Amp
4 or 5 Terminal
GENERAL APPLICATIONS
SPECIAL APPLICATIONS
PEDESTAL STYLE


GENERAL APPLICATIONS

MFG. & CATALOG #

5th TERMINAL ACCESSORY IF REQ'D
(
SEE NOTE #4)

SERVICE AMPS

ENTRY

MAX UG WIRE SIZE

CUTLER HAMMER

CHMMB100BTS*

Removable

100

OH

----

CHMMB200BTS*

Removable

200

OH

UG

350MCM

LANDIS & GYR

LGMM0202B1125RJB*

Removable

100

OH

NA

LGMM0202B1125RJBX*

Removable

100

OH

NA

LGMM0202B1200RJB*

Removable

200

OH

NA

LGMM0202B1200RJBX*

Removable

200

OH

NA

MIDWEST

R-100C with MSBN1

MS5

100

OH

----

RS-250C with MSBN2

MS5

200

OH

----

MURRAY

JB424S

NA

320

UG

750mcm

JC0404L1400RLM*

NA

320

OH

NA

JA0816B1400RLTM

NA

320

OH

NA

JC0202B1125RJB*

Removable

100

OH

NA

JC0202B1125RJBX*

Removable

100

OH

NA

JC0202B1200RJB*

Removable

200

OH

NA

JC0202B1200RJBX*

Removable

200

OH

NA

JC0406L1200RHJB

Removable

200

OH

NA

SIEMENS

MC2440MB22L

NA

320

UG

750mcm

MM0404L1400RLM*

NA

320

OH

NA

MC0816B1400RLTM

NA

320

OH

NA

MM0202B1125RJB*

Removable

100

OH

NA

MM0202B1125RJBX*

Removable

100

OH

NA

MM0202B1200RJB*

Removable

200

OH

NA

MM0202B1200RJBX*

Removable

200

OH

NA

MM0406L1200RHJB

Removable

200

OH

NA

* Not for mobile home installations.

 

SPECIAL APPLICATIONS

APPLICATION

MFG. & CAT. #

5th TERMINAL ACCESSORY IF REQ'D
(
SEE NOTE #4)

SERVICE AMPS

ENTRY

ADDITIONAL INFORMATION
(
SEE NOTE #6)

Meter Socket/Double Throw Breaker Combination for Customer's Standby Power Generating Equipment

Durham #UHSB204DT100N

N/A

200

OH Only

200A Main Breaker 100A Generator Breaker with sliding beam double throw handle assembly

* Equipment must be listed for use as service entrance equipment per NEC.

 

PEDESTAL STYLE

MFG. &
CATALOG #

ACCESSORY
REQUIRED

5th TERMINAL
REQUIRED

SERVICE
AMPS

AIC

MILBANK (View picture of pedestal style bases in this table)

CP3B511–ML & SL Series

CP-16PDMNT-CALT

NA

200

22KA

CP3B512–ML & SL Series CP-16PDMNT-CALT

K3865

200
22KA
CP3B521–ML & SL Series CP-16PDMNT-CALT

NA

200
22KA
CP3B522–ML & SL Series CP-16PDMNT-CALT

K3865

200
22KA
CP3B531–ML & SL Series CP-16PDMNT-CALT

NA

200
22KA
CP3B532–ML & SL Series CP-16PDMNT-CALT

K3865

200
22KA

 

MOST RECENT CHANGES

DATE

MFG.

CATALOG #

STATUS

REASON

4/2008

Milbank

CP3B511-ML & SL Series
CP3B512-ML & SL Series
CP3B521-ML & SL Series
CP3B522-ML & SL Series
CP3B531-ML & SL Series
CP3B532-ML & SL Series

Addition

New

NOTES:

1.

The manufacturer's catalog number must be stamped on the outside of the meter base or on a sticker inside the base so that it will be visible after the base is installed. The number must not be stamped on the cover.

2.

Meter bypasses:

(a)

Horn bypasses are required on 100 and 200 amp bases.

 

 

(b)

All Class 320 meter bases must contain a lever bypass rated 100% continuous duty.

3.

Service equipment:

The main breaker(s) and all branch breakers must have a 10,000 amp interrupting capacity minimum.

The neutral in the service compartment must be bondable and have a provision for the connection of a grounding electrode conductor.

When used as Mobile Home Service Equipment provisions must be provided for connecting additional equipment outside the mobile home by a fixed wiring method as per NEC requirements. In addition to the main breakers(s), the equipment must be capable of accommodating 2-2 pole or 4-1 pole, or 1-2 pole and 2-1 pole circuit breakers.

4.

Meter bases used for 208/120 volt, 3 wire services must have a 5th terminal installed in the 9 o'clock position. The catalog number for the 5th terminal is listed in the "5th Terminal Accessory" column in the table and must be specified when purchasing the meter base.

5.

When aluminum conductors are used, the electrical contractor must apply the corrosion inhibiting compound recommended by and in the manner prescribed by the cable manufacturer.

6.

Can be used where fault current is 10,000 amps or less.