TABLE 11
(print from .pdf)
Effective April 15, 2008 Updates All Previous Tables |
|
|
|
SINGLE PHASE, SINGLE POSITION METER SOCKET/LOAD CENTER OVERHEAD & UNDERGROUND ENTRANCE 120/240 or 208/120 Volt 100, 200 or 320 Amp 4 or 5 Terminal GENERAL APPLICATIONS SPECIAL APPLICATIONS PEDESTAL STYLE
|
GENERAL APPLICATIONS
|
MFG. & CATALOG # |
5th TERMINAL ACCESSORY IF REQ'D (SEE NOTE #4) |
SERVICE AMPS |
ENTRY |
MAX UG WIRE SIZE |
|
CUTLER HAMMER |
|
CHMMB100BTS* |
Removable |
100 |
OH |
---- |
|
CHMMB200BTS* |
Removable |
200 |
OH |
UG |
350MCM |
| LANDIS & GYR |
|
LGMM0202B1125RJB* |
Removable |
100 |
OH |
NA |
|
LGMM0202B1125RJBX* |
Removable |
100 |
OH |
NA |
|
LGMM0202B1200RJB* |
Removable |
200 |
OH |
NA |
|
LGMM0202B1200RJBX* |
Removable |
200 |
OH |
NA |
|
MIDWEST |
|
R-100C with MSBN1 |
MS5 |
100 |
OH |
---- |
|
RS-250C with MSBN2 |
MS5 |
200 |
OH |
---- |
|
MURRAY |
|
JB424S |
NA |
320 |
UG |
750mcm |
|
JC0404L1400RLM* |
NA |
320 |
OH |
NA |
|
JA0816B1400RLTM |
NA |
320 |
OH |
NA |
|
JC0202B1125RJB* |
Removable |
100 |
OH |
NA |
|
JC0202B1125RJBX* |
Removable |
100 |
OH |
NA |
|
JC0202B1200RJB* |
Removable |
200 |
OH |
NA |
|
JC0202B1200RJBX* |
Removable |
200 |
OH |
NA |
|
JC0406L1200RHJB |
Removable |
200 |
OH |
NA |
|
SIEMENS |
|
MC2440MB22L |
NA |
320 |
UG |
750mcm |
|
MM0404L1400RLM* |
NA |
320 |
OH |
NA |
|
MC0816B1400RLTM |
NA |
320 |
OH |
NA |
|
MM0202B1125RJB* |
Removable |
100 |
OH |
NA |
|
MM0202B1125RJBX* |
Removable |
100 |
OH |
NA |
|
MM0202B1200RJB* |
Removable |
200 |
OH |
NA |
|
MM0202B1200RJBX* |
Removable |
200 |
OH |
NA |
|
MM0406L1200RHJB |
Removable |
200 |
OH |
NA |
* Not for mobile home installations.
SPECIAL APPLICATIONS
|
APPLICATION |
MFG. & CAT. # |
5th TERMINAL ACCESSORY IF REQ'D (SEE NOTE #4) |
SERVICE AMPS |
ENTRY |
ADDITIONAL INFORMATION (SEE NOTE #6) |
|
Meter Socket/Double Throw Breaker Combination for Customer's Standby Power Generating Equipment |
Durham #UHSB204DT100N |
N/A |
200 |
OH Only |
200A Main Breaker 100A Generator Breaker with sliding beam double throw handle assembly |
|
* Equipment must be listed for use as service entrance equipment per NEC. |
PEDESTAL STYLE
|
MFG. & CATALOG # |
ACCESSORY REQUIRED |
5th TERMINAL REQUIRED |
SERVICE AMPS |
AIC |
| MILBANK (View picture of pedestal style bases in this table) |
|
CP3B511–ML & SL Series |
CP-16PDMNT-CALT |
NA |
200 |
22KA |
| CP3B512–ML & SL Series |
CP-16PDMNT-CALT |
K3865 |
200 |
22KA |
| CP3B521–ML & SL Series |
CP-16PDMNT-CALT |
NA |
200 |
22KA |
| CP3B522–ML & SL Series |
CP-16PDMNT-CALT |
K3865 |
200 |
22KA |
| CP3B531–ML & SL Series |
CP-16PDMNT-CALT |
NA |
200 |
22KA |
| CP3B532–ML & SL Series |
CP-16PDMNT-CALT |
K3865 |
200 |
22KA |
|
DATE |
MFG. |
CATALOG # |
STATUS |
REASON |
|
4/2008 |
Milbank |
CP3B511-ML & SL Series CP3B512-ML & SL Series CP3B521-ML & SL Series CP3B522-ML & SL Series CP3B531-ML & SL Series CP3B532-ML & SL Series |
Addition
|
New
|
|
NOTES: |
|
1. |
The manufacturer's catalog number must be stamped on the outside of the meter base or on a sticker inside the base so that it will be visible after the base is installed. The number must not be stamped on the cover. |
|
2. |
Meter bypasses: |
(a) |
Horn bypasses are required on 100 and 200 amp bases. |
|
|
|
(b) |
All Class 320 meter bases must contain a lever bypass rated 100% continuous duty. |
|
3. |
Service equipment: |
The main breaker(s) and all branch breakers must have a 10,000 amp interrupting capacity minimum.
The neutral in the service compartment must be bondable and have a provision for the connection of a grounding electrode conductor.
When used as Mobile Home Service Equipment provisions must be provided for connecting additional equipment outside the mobile home by a fixed wiring method as per NEC requirements. In addition to the main breakers(s), the equipment must be capable of accommodating 2-2 pole or 4-1 pole, or 1-2 pole and 2-1 pole circuit breakers. |
|
4. |
Meter bases used for 208/120 volt, 3 wire services must have a 5th terminal installed in the 9 o'clock position. The catalog number for the 5th terminal is listed in the "5th Terminal Accessory" column in the table and must be specified when purchasing the meter base. |
|
5. |
When aluminum conductors are used, the electrical contractor must apply the corrosion inhibiting compound recommended by and in the manner prescribed by the cable manufacturer. |
|
6. |
Can be used where fault current is 10,000 amps or less. |
|
|
|