Table 4
(print from .pdf)
Effective March 10, 2009 Updates All Previous Tables |
|
Polyphase, Single Position UNDERGROUND ENTRANCE 200, 400, or 600 Amp, 208/120 Volt Wye or 240/120 Volt Delta 200, or 400 Amp, 480/277 Volt Wye 7 Terminal
|
|
MFG. & CATALOG # |
SERVICE AMPS |
DIMENSIONS (INCHES) HxWxD |
TERMINAL SIZE (AWG OR KCMIL) |
BYPASS TYPE |
MAX UG WIRE SIZE |
|
|
|
|
MIN. |
MAX |
See Note #2 |
|
|
CUTLER HAMMER |
|
1004138A-CH |
200 |
34 x15x15  |
4 |
500 |
Lever |
500 |
|
DURHAM |
|
1004138A |
200 |
34 x15x5  |
4 |
500 |
Lever |
500 |
|
LANDIS & GYR |
|
9804-9142 (side-wired) |
200 |
20 x16 x5 |
4 |
600 |
Lever |
350 |
|
44707-02PP (side-wired) |
400 (Cl 320) |
34x20x6 |
See Note #8 |
Lever |
750 |
|
9817-9802 (side-wired) |
600 (Cl 480) |
37 x26 x7 |
See Note #9 |
Bolt-In |
--- |
|
MILBANK |
|
U-3786 (side-wired) |
200 |
19x18x6 |
6 |
350 |
Lever |
350 |
|
U-4168 (side-wired) |
400 (Cl 320) |
34 x19x6 |
See Note #8 |
Lever |
750 |
|
SIEMENS |
|
S9804-9096 (side-wired) |
200 |
20 x16 x5 |
4 |
600 |
Lever |
350 |
|
S9804-9142 (side-wired) |
200 |
20 x16 x5 |
4 |
600 |
Lever |
350 |
|
S44707-02PP (side-wired) |
400 (Cl 320) |
34x20x6 |
See Note #8 |
Lever |
750 |
|
S9817-9802 (side-wired) |
600 (Cl 480) |
37 x26 x7 |
See Note #9 |
Bolt In |
--- |
|
SQUARE D |
|
1004138A-SQD |
200 |
34 x15x15  |
4 |
500 |
Lever |
500 |
480V CIRCUIT BREAKER/METER BASE COMBINATION
|
MFG. & CATALOG # |
SERVICE AMPS |
DIMENSIONS (INCHES)
|
LINE TERMINAL SIZE (AWG OR KCMIL) |
LOAD TERMINAL SIZE (AWB OR KCMIL) |
AIC @480V |
|
HxWxD |
MIN |
MAX |
MIN |
MAX |
| MILBANK |
|
U5787-0-200-CB |
200 |
28x26x5 |
#1/0 |
350 |
#6 |
350 |
35,000 |
MOST RECENT CHANGES
|
DATE |
MFG. |
CATALOG # |
STATUS |
REASON |
|
12/2008 |
Milbank |
U5787-0-200-CB |
Approved |
New |
|
NOTES: |
|
1. |
All meter bases listed in this table are "ringless" style and are rated 600 volts AC unless otherwise noted. |
|
2. |
All polyphase socket style bases must contain a lever bypass rated 100% continuous duty. |
|
3. |
The manufacturer's catalog number must be stamped on the outside of the meter base so that it will be visible after the base is installed. The number must not be stamped on the cover. |
|
4. |
When aluminum conductors are used, the electrical contractor must apply the corrosion inhibiting compound recommended by and in the manner prescribed by the cable manufacturer. |
|
5. |
All 200 amp meter bases capable of accepting 500 Kcmil conductor must be marked "200 Amp Capacity". |
|
6. |
The third jaw from the left (as viewed from the front) on the bottom row of the seven jaw block must be connected to the neutral using a #14 awg or larger copper wire. |
|
7. |
Conduit Requirements:
- 200 Amp Service - The conduit KO directly under the line (utility) terminals must accept a 3 inch conduit.
- 400 Amp (Cl 320) Service - The conduit KO directly under the line (utility) terminals must accept a 4 inch conduit. The conduit KOs directly under the load terminals must accept two(2) 3 1/2 inch conduits.
- 600 Amp (Cl 480) Service - The conduit KOs directly under the line (utility) terminals must accept two (2) 4 inch conduits. The conduit KOs directly under the load terminals must accept an additional two (2) 4 inch conduits.
|
|
8. |
Class 320 Meter Bases:
- All 320 amp meter bases contain stud terminals.
- Only UL approved lay-in or box style connectors suitable for use with copper or aluminum conductors can be installed for wire termination on the studs.
- Compression connectors are not permitted.
- The upper right hand jaw (as viewed from the front) must contain an "anti-inversion" insert to prevent inverted meter installation or installation of a lower class meter.
|
|
CLASS 320 METER BASE CONNECTOR REQUIREMENTS |
| |
LINE SIDE TERMINALS |
LINE SIDE NEUTRAL TERMINALS |
LOAD SIDE TERMINALS |
| WIRE RANGE |
Single Only 350 to 750 Kcmil |
4/0 Awg to 500 Kcmil |
Single--Up to 600 Kcmil Double--Up to 350 Kcmil |
|
APPROVED CONNECTORS FOR CLASS 320 METER BASES |
|
MFG. |
LINE SIDE TERMINALS |
LINE SIDE NEUTRAL TERMINALS |
LOAD SIDE TERMINALS |
|
LANDIS & GYR, SIEMENS |
56476 |
60162 |
Single - 60162 Double - 56732 |
|
MILBANK |
K3863 |
K1540 |
Single - K1540 Double - K1350 |
|
9.
|
Class 480 Meter Bases:
- All 480 amp meter bases contain stud terminals.
- Only L&G anti-rotational, box-style connectors can be installed for wire termination on the studs.
- Compression connectors are not permitted.
- Single or double port terminals are permitted on the line side studs.
- Single, double or triple port terminals are permitted on the load side studs.
|
|
APPROVED CONNECTORS FOR CLASS 480 METER BASES |
|
MFG. |
LINE SIDE TERMINALS |
LINE SIDE NEUTRAL TERMINALS |
LOAD SIDE TERMINALS |
|
LANDIS & GYR, SIEMENS |
Single Port Kit |
|
3 - #56476 (3/0-800 Kcmil) |
1 - #60162 (#4-600 Kcmil) |
3 - #56476 (3/0-800 Kcmil) 1 - #60162 (#4-600 Kcmil) |
|
Double Port Kit |
|
3 - #56732-M (#4-500 Kcmil) |
1 - #56732-M (#4-500 Kcmil) |
4 - #56732-M (#4-500 Kcmil) |
|
Triple Port Kit |
|
Not Permitted |
Not Permitted |
4 - #68752-1 (#6-250 Kcmil) |
|
|
|