RULE 12 - METERS -- GENERAL
|
| a. |
Customer Provides Space: |
|
|
The customer provides space to accommodate PPL EU's meters at the point of service or nearest location designated by PPL EU. The meters must be accessible to PPL EU employees. |
| b. |
Capacity Determined by PPL EU: |
|
|
PPL EU specifies the capacity and type of meter installation required to accommodate the customer's load and type of service. |
| c. |
Customer Installs Meter Mounting: |
|
|
The customer installs the meter base or meter panel. The meter base or meter panel must be securely fastened on a wall or other support structure and must be level, plumb and vibration free.
Meter bases and meter panels mounted on masonry surfaces must be secured using non-corrosive metal machine screws in lead sleeve wedge-type expansion anchors (1/4 inch minimum). Meter bases and meter panels mounted on wood surfaces must be secured using non-corrosive wood screws (#12 minimum) into the support studs. |
| d. |
PPL EU Installs, Relocates or Removes All Meters: |
|
|
Only PPL EU authorized personnel can install, remove or relocate a meter.
The customer makes all necessary changes in wiring before PPL EU moves a meter to a new location. |
| e. |
Metered and Unmetered Conductors Not In The Same Raceway: |
|
|
Metered and unmetered conductors shall not be installed in the same conduit or raceway. |
| f. |
Metering Equipment Not Used As Junction and/or Pull Box: |
|
|
Meter bases and the termination compartments of multiple position meter bases shall not be used as junction and/or pull boxes.
All metering equipment including but not limited to meter panels, meter bases, termination compartments, instrument transformer compartments, and instrument transformer cabinets shall not be used as junction and/or pull boxes.
Splices (bugs) are not permitted in any equipment mentioned in the prior paragraph.
See Rule 15 for instrument transformer cabinets. |
| g. |
Protective Barriers: |
|
|
PPL EU may require customer to install barriers to protect metering from vehicular traffic. |
| h. |
Foreign Source/Power: |
| |
Foreign Source/Power and all associated wiring shall not be permitted in any PPL EU metering or Termination Equipment. |
| i. |
Sealing of Equipment: |
| |
PPL EU reserves the right to seal meter panels, meter bases, termination compartments, instrument transformer cabinets, wire troughs, junction and/or pull boxes and any other equipment containing unmetered conductors in any manner that PPL EU sees fit. |