Table 6

Approved Meter Service Devices

(print from .pdf)

Effective September 1, 1997
Updates All Previous Tables

POLYPHASE
2 to 6 positions
Overhead & Underground Entrance
208/120 Volt Wye or 240/120 Volt Delta
200 Amp
7 Terminal

 

MFG. &
CATALOG#

SERVICE AMPS

NUMBER OF POSITIONS

WIRING COMPARTMENT LOCATION

MILBANK

S-9098

200

2

Center

 

MOST RECENT CHANGES

DATE

MFG.

CATALOG #

STATUS

REASON

 

 

 

 

 

 

NOTES:

1. All meter bases listed in this table are "ringless" style.
2.  All polyphase socket style bases must contain a lever bypass rated 100% continuous duty. 
3.  The manufacturer's catalog number must be stamped on the outside of the meter base so that it will be visible after the base is installed. The number must not be stamped on the cover. 
4.  When aluminum conductors are used, the electrical contractor must apply the corrosion inhibiting compound recommended by and in the manner prescribed by the cable manufacturer. 
5.  The third jaw from the left (as viewed from the front) on the bottom row of the seven jaw block must be connected to the neutral using a #14 awg or larger copper wire.